Generator Maintenance Log by Hours
A generator maintenance log records every service with the date, engine hours, what was done and the load it was running. Most diesel generators need oil and filter around every 100–250 hours (with a calendar limit for standby units), fuel and air filters around every 250–500 hours, and coolant and belt checks on a schedule. These are typical ranges; your generator's manual sets the exact intervals.
Jobsite vs standby generators
Jobsite generators run long days and rack up hours quickly. Hours are the main trigger for service.
Standby generators may run only during tests and outages. They hit calendar limits before hour limits, and their biggest risks are dead batteries, stale fuel and failure to start when needed. Log hours anyway, plus every test run.
Typical service intervals
| Interval | Typical items | Notes |
|---|---|---|
| Daily / before use | Oil and coolant levels, fuel level, leaks, battery, air intake clear | Jobsite units |
| 50 hours | Check belts and hoses, drain water from fuel/water separator | First oil change on new units per manual |
| 100–250 hours | Engine oil and filter | Or annually for standby units |
| 250–500 hours | Fuel filters, air filter, check valve clearance where specified | Shorter in dusty sites |
| 500–1,000 hours | Coolant test or change, belt replacement, load bank test | Many standby units: annually |
| Annually | Full inspection, battery test, transfer switch check (standby) | Plus any local requirements |
Light-duty load is its own problem. Diesel generators that run for long periods at a small fraction of rated load can suffer from wet stacking, where unburned fuel builds up in the exhaust. If your generator mostly runs lightly loaded, ask your dealer about periodic load testing.
What to record in the log
- Date and engine hours at each service and each run period.
- Work done: oil and filter, fuel filter, air filter, coolant, belts.
- Load: approximate load or what it was powering ("light tower and two pumps").
- Fuel added, in gallons.
- Problems: hard starts, warning lights, leaks, voltage fluctuations.
- Test runs for standby units: date, duration, whether it carried load.
Generators also get moved around and lent between jobs, so record which site it was at. Hour meters fail on generators too; see what to do if an hour meter is reset or replaced.
Example log entries
| Date | Hours | Entry |
|---|---|---|
| Mar 2 | 1,180 | Oil and filter, checked belts |
| Mar 19 | 1,265 | Fuel 48 gal, running pumps on Elm St. site |
| Apr 6 | 1,402 | Fuel filter, air filter, drained separator |
| Apr 20 | 1,470 | Hard start in the morning, battery tested OK, checking glow plugs |
For how to turn hour readings into a running schedule, see our engine hours maintenance schedule.
How to keep it going
In Equipment Maintenance Log, each generator has its own chat, alongside your trucks and machines. After service: "Generator 2, changed oil and filter, 1,180 hours." At fill-up: "Generator 2, 48 gallons, 1,265 hours, running pumps on Elm Street." The AI assistant saves the work, readings and date, and reminders for the next oil change are based on the hours you log. AI can make mistakes, so every entry can be reviewed and corrected.
FAQ
How often should a generator get an oil change?
Typical intervals run from about 100 to 250 hours for diesel units, with an annual limit for standby generators that run little. Check your manual and shorten the interval in dusty or heavy-load work.
How do I log hours on a generator without an hour meter?
Log start and stop times for each run and add them up, or install an hour meter. Estimated hours should be marked as estimates.
Should standby generators be run regularly?
Many manufacturers recommend regular exercise runs, ideally under load. Log each test with date, duration and any problems.
What is wet stacking?
A buildup of unburned fuel in the exhaust of diesel generators that run for long periods at light load. Periodic running under a heavier load usually helps; ask your dealer.